SAFETY-18: verify on the real rig, and record what it showed
AC3 says "verified on the rig". The previous commit drove hwsim in-process because `riglock status` reported UNKNOWN - which is the tool declining to observe, not an observation. riglock shells out to the local docker CLI; on a Windows host without DOCKER_HOST that resolves to a Docker Desktop npipe which is not running, and the result is indistinguishable from a genuinely absent rig. The rig was up the whole time. With DOCKER_HOST=ssh://homelab@192.168.2.147 it reads FREE. Re-run under sim/riglock.py against the real goodwe-sim compose project, with the shipped modules staged into goodwe-sim-plant so they poll that container's own hwsim while plantsim drives it. Both phases passed, lock released cleanly. The rig produced a result the in-process stub could not, and it strengthens the design rather than merely confirming it: in the NEGATIVE twin - +8000 W of house load, healthy meter, correctly railed command - `active_power_w` did not move at all, sitting at exactly 10130.0 W for 26 consecutive polls. The only thing keeping `unchanged_s` at 0.0 s was the kWh registers advancing. So the register terms in measurement_fingerprint() are not belt-and-braces for this detector, they ARE the negative case: fingerprinted on the power figure alone it would have raised a false alarm on a healthy meter under a real load, which is precisely how a safety guard gets switched off. Recorded in freeze.py so nobody simplifies the fingerprint without meeting that run first. No behaviour change - documentation and the harness note only. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC
This commit is contained in:
co-authored by
Claude Opus 5
parent
7aa1bd052e
commit
0ba3a200fe
@@ -71,6 +71,20 @@ meter, and a kilowatt advances a 1 Wh register every 3.6 s.
|
||||
|
||||
The two terms fail for independent reasons. That is the whole design.
|
||||
|
||||
⚠️ AND THE SECOND HALF OF THAT WAS MEASURED ON THE RIG, WITH A RESULT WORTH
|
||||
READING CAREFULLY. Driving the real transport against the rig's own hwsim under
|
||||
+8000 W of house load - a genuinely railed command, meter perfectly healthy - the
|
||||
POWER FIGURE DID NOT MOVE AT ALL: `active_power_w` sat at exactly 10130.0 W for
|
||||
26 consecutive polls. What kept `unchanged_s` pinned at 0.0 s was the kWh
|
||||
registers advancing, and nothing else.
|
||||
|
||||
So the register terms in `measurement_fingerprint()` are not belt-and-braces
|
||||
here, they are the entire negative case. A freeze detector fingerprinted on the
|
||||
power figure alone would have raised a false alarm on that rig run - a healthy
|
||||
meter, a real load, a correctly railed command - which is the exact failure mode
|
||||
that gets a safety guard switched off. Anyone tempted to simplify the fingerprint
|
||||
should read that run first.
|
||||
|
||||
------------------------------------------------------------------------------
|
||||
WHERE `hold_s` COMES FROM
|
||||
|
||||
|
||||