TEL-01 review fixes: stop the age sensor tripping installs that have no meter
T-1, and it was a fleet-wide trip to zero. publish() emitted p1_age unconditionally, and published_age_s counts from P1Ingest.__init__ when no sample has ever arrived. With meter_source defaulting to off, every existing install would have published sensor.p1_sample_age_s climbing without bound; the ESP32 does `has_state() && state >= max_age_s` and forces the layer-1 failsafe, so each of them would have pinned its inverter at 0 W within 30 s. Exactly the opposite of the zero-regression the off default was for. The key is now omitted from the payload AND from MQTT discovery when P1 is off, so the entity does not exist at all - which is the status quo, and what has_state() is testing for. The predicate is one function, is_enabled(), because the grid reading, the task start and the discovery announcement have to agree or this comes back. T-2, connect no longer manufactures a sample. get_states returns whatever HA currently holds, which after a Core restart is a RestoreEntity value of unknown age; stamping it with ingest_ts=now reset the age and reported a fresh meter that could have been dead for an hour. run()'s own docstring already said a reconnect must emit nothing - the code disagreed with it, and a test asserted the violation. The cache is still primed, so the first real state_changed builds a complete sample; the age just stays honest until one arrives. T-3, gaps are no longer filled with the last held value. The averager held a sample forward across any interval, so a meter dying at 5 kW and returning ten minutes later credited 5 kW x 600 s to the capacity-tariff accumulator - a fabricated peak on a permanent record. The hold is capped at max_age_s: past that the stretch is walked so block boundaries still land correctly, but nothing accumulates and elapsed does not grow, which is what finally makes the comment about a gap dragging the billed average down true. Same threshold for control and billing: a reading too old to steer by is too old to bill by. T-4, the out-of-order/duplicate guard is covered. It was untested, and the reason is worth recording: the obvious assertion passes without the guard, because the negative interval is separately refused by the covered > 0 test. What the guard prevents is the timestamp REWIND, which only shows up one sample later as a re-integrated window. The test now goes one sample later. T-6, DOCS was wrong about latency. meter_max_age_s and stale_input_s stack, so meter death to 0 W is 45 s and not 30. Documented as a table with both clocks. Also documented the T-5 asymmetry rather than papering over it: the age measures arrival, not change, so a stuck MQTT bridge republishing its last telegram still looks fresh. Correct on ha_dsmr, not detectable on mqtt_p1 without a change-detector. Written up as a known limit. Writing the T-1 test caught a second defect in the test itself: it recorded only MQTT topics, and object_id lives in the payload, so "the age sensor is not announced" had been passing for the wrong reason. test_p1.py: 99 -> 122 checks. 14 mutations run, all 14 red, files restored byte-identical - including one per fix above. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
This commit is contained in:
co-authored by
Claude Opus 5
parent
2097b7aaf6
commit
0a617c5482
@@ -39,7 +39,7 @@ from .control import Tuning, compute, maintenance_charge_floor, peak_at_risk
|
||||
from .hass import HomeAssistant
|
||||
from .maintenance import IDLE, MaintConfig, Maintenance
|
||||
from .mqtt import MqttPublisher
|
||||
from .p1 import P1Ingest, build_source
|
||||
from .p1 import P1Ingest, build_source, is_enabled
|
||||
from . import web
|
||||
|
||||
OPTIONS_PATH = "/data/options.json"
|
||||
@@ -96,7 +96,7 @@ class Controller:
|
||||
# until it opts in.
|
||||
self.p1 = P1Ingest(phases=int(opts.get("meter_phases", 1)),
|
||||
max_age_s=float(opts.get("meter_max_age_s", 30)))
|
||||
self.p1_enabled = str(opts.get("meter_source", "off")) not in ("off", "")
|
||||
self.p1_enabled = is_enabled(opts)
|
||||
|
||||
# live state
|
||||
self.auto = bool(store.data.get("auto", opts.get("auto_start", False)))
|
||||
@@ -324,16 +324,26 @@ class Controller:
|
||||
await asyncio.sleep(1)
|
||||
|
||||
def publish(self) -> None:
|
||||
self.mqtt.publish({
|
||||
values = {
|
||||
"setpoint": self.target,
|
||||
"grid": self.grid,
|
||||
"battery": self.batt,
|
||||
"soc": self.soc,
|
||||
"phase": self.maint.phase,
|
||||
"status": "running" if self.auto else "stopped",
|
||||
}
|
||||
# ⚠️ ONLY when P1 ingestion is actually running. The ESP32's stale-input
|
||||
# watchdog subscribes to sensor.p1_sample_age_s and forces the layer-1
|
||||
# failsafe once it reaches max_age_s. With meter_source off there is no
|
||||
# ingester feeding it, so published_age_s would be time-since-startup
|
||||
# climbing without bound - i.e. every existing install would cross the
|
||||
# threshold within 30 s and pin its inverter at 0 W forever. Publishing
|
||||
# nothing leaves the entity non-existent, which is the status quo and
|
||||
# what has_state() in the firmware is checking for.
|
||||
if self.p1_enabled:
|
||||
# Recomputed here, once a second, on purpose - see P1Ingest.
|
||||
"p1_age": round(self.p1.published_age_s, 1),
|
||||
})
|
||||
values["p1_age"] = round(self.p1.published_age_s, 1)
|
||||
self.mqtt.publish(values)
|
||||
|
||||
async def shutdown(self) -> None:
|
||||
"""Deterministic wind-down. Do not skip this."""
|
||||
@@ -501,6 +511,7 @@ async def amain() -> None:
|
||||
broker.get("port", 1883) if broker else 1883,
|
||||
broker.get("username") if broker else None,
|
||||
broker.get("password") if broker else None,
|
||||
omit=() if is_enabled(opts) else ("p1_age",),
|
||||
)
|
||||
except Exception as err: # noqa: BLE001
|
||||
_LOG.warning("MQTT unavailable (%s) - continuing without status entities", err)
|
||||
|
||||