SAFETY-128: control does not act on late Home Assistant readings
checks / unit (pull_request) Successful in 19m36s
infra-pin / fresh (pull_request) Successful in 1s

Readings that Home Assistant delivers late but still changing passed
every staleness gate, so the loop corrected again each cycle an error
its last command had already fixed (10 s late: the give run swung and
exported to -1.9 kW), and the peak guard pushed to the inverter limit
on the same late figures (OPT-34 F-2).

app/lateness.py fits how long after a power request the meter shows
it. Over 8 s the readings are late: a request the battery reading has
not answered holds the loop (it may not lead the reading by more than
100 W) and caps the peak guard at what stands; unanswered for 23 s it
holds, then 0 W after stale_input_s. An amber row and one log line per
episode say so. With readings on time nothing changes (digests equal).

DECISIONS/SAFETY-128-late-readings.md; test_safety128.py.

Co-Authored-By: Claude <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Bdqr7PiaHcBnzPituu2yTC
This commit is contained in:
glenn schrooyen
2026-11-01 23:45:03 +01:00
co-authored by Claude
parent 77fe31b161
commit 09e1fbb898
14 changed files with 1100 additions and 2 deletions
+52
View File
@@ -64,6 +64,7 @@ from .clamp import (
shortfall_note, write_clamp_note,
)
from . import freshness
from . import lateness
from . import dayview, homeview
from .daycurve import SolarToday
from . import messages
@@ -1281,6 +1282,8 @@ class Controller:
self.cycle_at = None
self._arb_action = None
self.inputs_bad_since = None
self.answer = lateness.Answer() # SAFETY-128
self._late_logged = self._late_zero = False
# SAFETY-03. What the loop's OWN bounds did last cycle - a
# (engaged, note) pair so the alarm can say WHICH bound bit without
# re-deriving it from a string. ⚠️ THIS ONE STAYS SITE-LEVEL, and it is
@@ -3116,6 +3119,36 @@ class Controller:
return (decision if self._peak_needed
else dataclasses.replace(decision, within_aim=True))
def _readings_late(self, standing_w):
"""SAFETY-128: update the answer gate; seconds the late verdict has
stood, or None. Readings found late are logged once per episode.
DECISIONS/SAFETY-128-late-readings.md."""
a = self.answer
if self._now_mono is None:
return None
a.observe(self._now_mono, standing_w, self.site_batt_w,
grid_w=self.grid, exempt=bool(self.batt_refused) or any(
i.refused or (
i.batt is not None
and abs(i.standing_w()) >= lateness.ANSWER_W
and abs(i.batt - i.idle_w) < lateness.ANSWER_W)
for i in self.inverters),
idle_w=self._site_idle_w())
if a.late_seen != self._late_logged:
self._late_logged = a.late_seen
if a.late_seen:
self.log_event(f"readings late ({a.delay_s:.0f} s) - holding",
hint=messages.hint("readings_late"))
_LOG.warning("Home Assistant readings arrive late, so control "
"holds the battery: READINGS_LATE.")
_LOG.debug("READINGS_LATE: the meter shows a power request "
"%.0f s after it is sent.", a.delay_s)
else:
self.log_event("readings on time", hint=messages.hint(
"readings_back"))
_LOG.info("Home Assistant readings are on time again.")
return a.late_s(self._now_mono)
def _peak_reserve(self) -> frozenset:
"""SAFETY-87: the batteries that give nothing for the peak this
cycle: under their reserve while the others carry a peak floor."""
@@ -4647,6 +4680,8 @@ class Controller:
"away a partly delivering unit's output.")
stale_after = float(self.o.get("stale_input_s", 15))
late_s = self._readings_late(site_standing) # SAFETY-128
self._late_zero = late_s is not None and late_s >= stale_after
# ⚠️ `any`, NOT the sole unit's. The hold exists so a single missed poll
# does not become a fault; a LATCHED inverter must still reach the claim
# list below, because its `failsafe` SET is what parks it. One tripped
@@ -4672,6 +4707,13 @@ class Controller:
self.why_words = messages.why_waiting(bad_for)
self._why_waiting_since = now - timedelta(seconds=bad_for)
return
if late_s is not None and late_s < stale_after and self.inputs_ok \
and (self.auto or self.shadow) \
and not any(i.sign_wd.tripped for i in self.inverters) \
and not (n_units > 1 and self.site_sign_wd.tripped):
self.reason = f"readings late {late_s:.0f}s" # SAFETY-128: hold
self.why_words = messages.why_late()
return
claims = []
@@ -4850,6 +4892,9 @@ class Controller:
hint=messages.hint("inputs_missing"))
claims.append(Claim.set("safety", P_SAFETY, 0.0, "inputs missing",
actuator=self.actuator_of("safety")))
elif late_s is not None:
claims.append(Claim.set("safety", P_SAFETY, 0.0, "readings late",
actuator=self.actuator_of("safety")))
# --- SAFETY-07: the quarter-peak projection guard --------------------
# ONE `lo` limit at P_PEAK, and peakguard.py carries the whole argument.
@@ -4973,6 +5018,8 @@ class Controller:
self.peak_guard = self._peak_on_able(self.peak_guard,
maint_results)
self.peak_guard = self._peak_landing(self.peak_guard)
self.peak_guard = peakguard.cap_floor( # SAFETY-128
self.peak_guard, self.answer.peak_cap(site_standing))
# SITE, and peakguard.claim() says so on the object it builds. The
# quantity is the 15-minute average OFFTAKE AT THE GRID CONNECTION,
# which is what the capacity tariff bills; there is one quarter-hour
@@ -5437,6 +5484,7 @@ class Controller:
if len(self.inverters) == 1 else None),
# SAFETY-97: "gives nothing" is centred on the idle reading.
idle_w=self._site_idle_w(),
hold=self.answer.hold, hold_w=self.answer.hold_w, # SAFETY-128
# OPT-11: None unless battery modes are on. SAFETY-85: or while
# maintenance holds a battery at N>=2, so the loop does not
# wind past what the others can give and jump when it ends.
@@ -7333,6 +7381,10 @@ class Controller:
(inv.refusal_note(), False)):
if note:
out.append({"ok": False, "warn": not red, "text": note})
if self.answer.late_seen: # SAFETY-128
out.append({"ok": False, "warn": True, "id": "late",
"text": messages.row_readings_late(
self.answer.delay_s, self._late_zero)})
# SAFETY-03. Red while an over-rating clamp is engaged (amber for the
# integrator bound, SAFETY-40), and the engagement COUNT is shown even