OPT-20: a refusal probe asks only PROBE_W, not the whole trade
checks / unit (pull_request) Failing after 40m47s
infra-pin / fresh (pull_request) Successful in 1s

The probe's trade was sized at the probing battery's rating. Its SAFETY-73
pin held 200 W of that, and the allocator put the rest on a battery with no
mode range (one in a maintenance phase): TEST-23 OPT-15 g7, -2300 W on A in
its maintenance charge for 34 s, grid 3100 W.

modetrade.decide() now asks PROBE_W for the probing battery plus what the
other chargers would have had without the probe; size() adds the probe on top
of their share, or files PROBE_W exactly, or nothing. _mode_trade() carries
the pin only on the ticks it is filed, so the window's first and last cycle
do not move another battery's share either. Modes off and modes on with no
probe are unchanged (bf9019e digests). Tests: test_opt20.py.

Co-Authored-By: Claude <noreply@anthropic.com>
This commit is contained in:
glenn schrooyen
2026-10-15 13:08:59 +02:00
co-authored by Claude
parent bf9019e70d
commit 06339a2446
5 changed files with 482 additions and 4 deletions
@@ -132,6 +132,23 @@ P1 is its section 6 P1, and the pull request lists what was measured.
own, and a rise past that is the peak floor's, which ends the hold.
A maintenance drain, hold or charge that starts during the hold ends it
on that tick (replayed at edge + 3 s).
- OPT-20 (TEST-23 OPT-15 g7, `test_opt20.py`): a probe asks only PROBE_W.
The trade was sized at the probing battery's rating (2500 W), B's pin held
200 W of it, and the allocator put the other 2300 W on A, in its
maintenance charge phase (no mode range there, so nothing kept it out):
grid 3100 W for 34 s. Now the ask is PROBE_W for the probing battery plus
what the other chargers would have had without the probe (none: 200 W
alone), and it carries the pin only on the ticks the pin is filed (the
window's first and last cycle moved another battery's share by 200 W).
- Chosen: the probe sits on top of a headroom-sized charge, so beside a
normal charger its command is the same and the grid rises 200 W (about
7 W on the quarter) rather than that charger giving 200 W up. A probe
that the headroom or the bound cannot hold at 200 W is not filed.
- Unchanged, same on bf9019e: with a charge ask the other batteries cannot
give (one sign), so an idle-looking A that gives the house stops for the
window and the grid rises by what it gave. The trade line now says 200 W
for a probe alone; its words are UX-38's. The base P4 F4 path (a normal
trade on a battery in maintenance charge) is not touched.